Technical Specifications:
Board Type: Safety Controller Processor Module
System: Triconex 3008
Architecture: Triple Modular Redundancy (TMR)
Processor: 32-bit RISC processor
Memory: 32MB RAM for application execution
Scan Time: 50 milliseconds per scan cycle
Communication: Dual TMRnet redundant paths to all I/O modules
Voting: Hardware 2-out-of-3 voting on every scan
I/O Support: Up to 256 I/O points per controller
Certifications: SIL 3, IEC 61508, IEC 61511
Power: 5V DC and 24V DC from backplane
Form Factor: 3U Triconex Eurocard
Functional Features:
Safety Logic Execution: Runs the safety application program that monitors process variables and initiates shutdown actions when unsafe conditions are detected.
Hardware Voting: Compares results from all three processors every 50ms; if one disagrees, it is removed from service automatically.
Dual Communication: Every processor has two independent communication paths to every I/O module, ensuring no single point of failure.
Online Diagnostics: Continuous self-testing with automatic fault detection and alarm reporting.
Fail-Safe Outputs: All safety outputs default to a safe state (de-energized) on loss of power or communication.
Application Flexibility: Supports complex safety logic including timers, counters, logic gates, and analog comparisons.